Jump to content

Storz

From Wikipedia, the free encyclopedia
Storz connector

Storz is a type of hose coupling invented by Carl August Guido Storz [de] in 1882 and patented in Switzerland in 1890, and patented in the U.S. in 1893[1] that connects using interlocking hooks and flanges. It was first specified in standard FEN 301-316, and has been used by German fire brigades since 1933. (See German delivery hose article.) Amongst other uses, it has been widely employed on fire hoses in firefighting applications. It is the standard coupling on fire hoses in Portugal, Denmark, Slovenia, Germany, Austria, Switzerland, Sweden, the Netherlands, Poland, Czechia, Israel, Croatia, Serbia, Bosnia & Herzegovina, Macedonia, Montenegro and Greece.[2] It is also one of the standard couplings on fire hoses in Australia and the United States.

The Storz coupling system is also widely used for filling of bulk wood pellet storage systems in Europe (Storz-A or 4-inch or 10-centimetre size), although in France and Belgium the equivalent Guillemin coupling is more commonly employed.

Storz connectors are usually made of brass or aluminium. They can be manufactured by casting for general hose connection and low pressure applications, but for firefighting, it is better to use forgings to guarantee the safety and durability of the coupling.

It is sometimes referred to as a sexless coupling, because rather than having a male and a female end connected by screw threads, either identical end can be joined to any other end of the same diameter. This is also called hermaphroditic or two-way connection. To couple a Storz connection, the two opposing couplings are pressed together such that the hooks of each one are inserted into the slots in the flange of the other. Then they are rotated in opposite directions until they are tight, or latches engage. This creates a watertight connection between the internal packing gaskets. To uncouple them, the latches are released and the connectors are turned in the opposite directions from coupling, and then separated when the hooks and slots are aligned. Special wrenches are designed for assisting with use of Storz connectors.

The main benefit to using Storz couplings is speed of hose connection, as a hose can be locked with a quarter-turn. By comparison, locking hoses using threaded couplings often takes several turns. Because of this, Storz couplings are widely viewed as a safer alternative to using threaded couplings. A secondary benefit over threaded couplings is that the connecting faces and hooks are less prone to damage if the coupling is dropped onto, or dragged over, a hard surface.

Storz couplers are available commercially in the following non-DIN-specified sizes:

Storz
size
Lug diameter,
inner face (mm)
Hose diameter,
internal (mm)
Standard Fire-fighting
usage
25 37 25 AS2419.4 Australia
32 44 32
38 52 38 CAN-ULC-S543, AS2419.4 Australia
45 59 45
65 81 38, 42, 52, 64, 70 CAN-ULC-S543, AS2419.4 Australia[3]
75 89 65, 75 AS2419.4
90 105 90 AS2419.4 Australia (legacy only)
100 115 101 (called 4″ in U.S.) CAN-ULC-S543, NFPA1963, AS2419.4 U.S.,[4] Australia
125 148 125 (called 5″ in U.S.) CAN-ULC-S543, NFPA1963, AS2419.4 U.S.,[4] Australia
135 159 135
150 3-lug 160 150 CAN-ULC-S543, AS2419.4 Australia
165 188 165
205 2-lug 220 203
205 3-lug
250 3-lug 278 256

DIN standards define the following pressure couplings:

Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
DIN
standard
Hose diameter,
internal (mm)
Fire-fighting
usage
D 25 31 14301 25 Germany
S28 52 66 14330-2 28 Germany
S32 14330-1 32 Germany
C42 14332 42 Germany
C52 14302 52 Germany
B 75 89 14303 75 Germany
A 110 133 14300 110

DIN standards define the following suction couplings:

Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
DIN
standard
Hose diameter,
internal (mm)
Fire-fighting
usage
D 25 31 14301 15, 19, 25
C 52 66 14321 19, 25, 32, 38, 42, 45, 52, 64
B 75 89 14322 52, 65, 70, 75
A 110 133 14323 102, 110 Germany

DIN standards define the following fixed couplings (for securing fittings to hoses):

Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
Sealing method DIN
standard
Fire-fighting
usage
D 25 31 Rubber gasket 14306
C 52 66 Rubber gasket 14307
Integral metal seat 14317
B 75 89 Rubber seal 14308
Integral metal seat 14318
A 110 133 Rubber gasket 14309
Integral metal seat 14319

DIN standards define the following threaded adapters:

Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
Thread DIN
standard
D 25 31 BSP 1″ 14306
C 52 66 BSP 2″ 14307
B 75 89 BSP 2+12 14308
A 110 133 BSP 4+12 14309

DIN standards define the following caps:

Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
DIN
standard
D 25 31 14310
C 52 66 14311
B 75 89 14312
A 110 133 14313

DIN standards define the following swivel reducers:

Induced Reduced DIN
standard
Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
Storz
size
Seal diameter,
inner (mm)
Lug diameter,
inner face (mm)
C 52 66 D 25 31 14341
B 75 89 C 52 66 14342
A 110 133 B 75 89 14343

United States usage

[edit]

Storz rapidly became a standard for fire hydrants throughout much of Europe, but it took nearly one hundred years before the main larger "steamer ports" on fire hydrants started to be converted to the Storz coupling in the United States. U.S. fire engines typically carry LDH (large diameter hose) with Storz couplings on both ends for connections between fire hydrants and pumps. However, if a hydrant usually has threaded couplings, an adapter is required to use with Storz. All major U.S. hydrant manufacturers now offer Storz couplings as original equipment on their hydrants, to connect with the Storz couplings used by firefighters. Hydrants may also be retro-fitted from thread to Storz to aid interoperability between firefighting organizations.

The 100 mm (4-inch) and 125 mm (5-inch) Storz couplers have been specified in NFPA 1963, Standard for Fire Hose Connections, since the 1993 edition.

U.S. cities that have fire hydrants with 125 mm Storz connectors include Raleigh, NC[5] and the City of Corvallis, OR (adapter on 4-inch threaded outlet).[6]

The 150 mm (6-inch) size is occasionally used for PVC suction hose, in place of the industry-standard 6 NH threads.

See also

[edit]

References

[edit]
  1. ^ "U.S. Patent US 489107 A". Retrieved 2 September 2017.
  2. ^ T.O.T.E.E. 2451/86 Εγκαταστάσεις σε κτήρια: Μόνιμα πυροσβεστικά συστήματα με νερό, Technical Chamber of Greece, 1986, pp. 12, 15, 20.
  3. ^ "FRNSW compatible hose connections" (PDF). Retrieved 2017-10-11.
  4. ^ a b "NFPA 1963" (PDF). Retrieved 2017-10-11.
  5. ^ "Standard Fire Hydrant with 5" Storz Pumper Nozzle - City of Raleigh" (PDF). Retrieved 1 September 2017.
  6. ^ "Fire Hydrants - City of Corvallis, OR". Retrieved 1 September 2017.
  • U.S. patent 489,107 The U.S. Patent Carl August Guido Storz was granted in 1893.
  • AS2419.4: "Fire hydrant installations, Part 4: Storz connections for firefighting purposes" (2020)
  • CAN-ULC-S543: "Standard for internal lug quick-connect couplings for fire hose" (2009)
  • DIN 14330: "Aluminium alloy delivery coupling type C nominal pressure PN 16" (2012)
  • DIN 14301: "Aluminium alloy delivery and suction coupling type D; nominal pressure" (1985)
  • DIN 14302: "Aluminium alloy delivery coupling type C; nominal pressure 16" (1985)
  • DIN 14303: "Aluminium alloy delivery coupling type B with nominal pressure PN 16" (2013)
  • DIN 14323: "Aluminium alloy delivery and suction coupling type A; nominal pressure 16" (1985)
  • DIN 14332: "Aluminium alloy delivery coupling type C; nominal pressure 16; used for fire hoses C 42" (1986)